UPS Sizing Calculator

Add up the wattage of your PCs, monitors, router, NAS and CCTV, choose the backup time you need and get the UPS VA rating and battery capacity for a home or office in Mumbai's power cuts.

Runs in your browser · Nothing stored

What the UPS must keep running

Recommended UPS
3 kVA online
Connected load975 W
VA needed (0.6 PF, 25% headroom)2,031 VA
Battery for the runtime6 × 12 V 9 Ah (calc. 8.5 Ah each)
UPS typeOnline double-conversion: zero transfer time, clean sine wave

Keep the UPS under 70 to 80% load so it lasts, never plug a laser printer into the battery outlets (its fuser spikes to 1,000 W), and replace sealed batteries every 2 to 3 years; Mumbai humidity and frequent MSEDCL cuts shorten their life. For runtimes above an hour, an inverter with tubular batteries is cheaper per minute than UPS batteries, with the UPS in front of the computers for the switch-over.